Analysis of Low Voltage Cabinet and Medium Voltage Cabinet
Aug 31, 2023
Analysis of Low Voltage Cabinet and Medium Voltage Cabinet
Low voltage capacitor cabinet is different from medium voltage capacitor. Medium voltage capacitor cabinet generally refers to the capacitor outlet cabinet, which means that the outlet cable is connected to the capacitor device to control and protect the capacitor. Similarly, there are grounding transformer cabinets. The capacitor device is installed in a fence or box, equipped with separate equipment such as isolation switches, contactors, reactors, capacitors, etc., placed in a separate area, not in the same row as the medium voltage switchgear. The low voltage capacitor cabinet actually installs capacitors in the cabinet, using contactors or composite switches for control depending on the control method, and installing ordinary cylindrical capacitors or smart capacitors.
Unlike the large size of medium voltage circuit breakers, a low voltage cabinet can only install one or two circuit breakers (double layer cabinets) as outgoing circuits. Low voltage switchgear generally can install several to more than ten circuit breakers, such as four frame circuit breakers or 12 molded case circuit breakers. Similar to the medium voltage withdrawable switchgear, the low-voltage frame circuit breaker in the switchgear also adopts a withdrawable structure, with a base fixed on the switchgear, including primary and secondary contacts, valves, guide rails, and other mechanisms. The withdrawable body achieves the connection and disconnection of the primary and secondary circuits through the swing in mechanism.
There are two types of low-voltage outgoing cabinets: fixed partition type and drawer type.
Low voltage fixed and separated circuit breakers adopt plug-in or withdrawable molded case circuit breakers. The plug-in base is fixed on the switchgear, and the branch busbar is connected to the main busbar. The plug-in molded case has mechanical interlocking, and the circuit breaker can only be pulled out of the base when it is opened. Medium voltage fixed switchgear circuit breakers are fixed circuit breakers that need to be used in conjunction with isolation switches, That is to say, the circuit breaker does not have an isolation function (the isolation load switch has an isolation function), so it must have an isolation switch and operating mechanism. The circuit breaker and the isolation switch are mechanically interlocked, and the isolation switch can only close the circuit breaker when it is closed, and the circuit breaker can only open the isolation switch when it is opened.
The low-voltage drawer cabinet is installed with molded case circuit breakers, current transformers, indicator lights, multifunctional meters, etc. on the drawer. A drawer is an outlet circuit, small drawers can be directly inserted into the board, while large drawers generally have a swing in mechanism. For the motor control circuit, drawers can be equipped with contactors, thermal relays, and other starting methods such as forward and reverse rotation, star delta, etc. The medium voltage motor control adopts a combination of contactors and fuses installed on the handcart, which can generally only be started directly. For forward and reverse rotation, it is more complex to require multiple contactors, and several medium voltage cabinets need to be used together.
The medium voltage switchgear has a grounding switch for grounding protection during maintenance and repair. The low voltage switchgear does not have a grounding switch, and the 380V low voltage switchgear can be directly connected to a grounding wire for safety protection.
The protection level is applicable to medium voltage cabinets and low voltage cabinets. The concept of losing operational continuity LSC in medium voltage cabinets is to determine the power outage range during maintenance based on the type of internal separation. Generally, the LSC level of metal armored withdrawable switchgear is 2B, which means that the main busbar can be live when maintaining the cable room. Low voltage cabinets come in the form of FORM, which is a separation type. FORM 4b achieves complete separation of functional units for all circuits, including cable connections for each outgoing line. The medium voltage cabinet has internal arc fault levels such as IAC AFLR, and the low voltage switchgear also needs to meet internal arc faults. However, there are definitions such as non arcing zones, and relatively speaking, the arcing energy of the low voltage switchgear is much smaller.
The medium voltage cabinet emphasizes the safety of high voltage, while the low voltage switchgear emphasizes the convenience of operation and maintenance
PRODUCT LINK
http://www.switchgear-china.com/switchgear/low-voltage-switchgear/low-voltage-electrical-control-panel-board.html
PRODUCT PHOTO








This product is usually customized.
We are a manufacturer and have a professional technical department that can design and provide solutions according to customer needs.
Please click on the button below to send us the information, and our sales personnel will contact you to provide you with the design drawings
Here are our customer examples for your reference
Kazakhstan Customers
| GCS LV Withdrawable Switchgear | ||
| S.N. | Specifications | Yes/No/If any |
| Electrical Panel (Low-voltage withdrawable switchgear cabinet) | ||
| Manufacturer | ||
| Brand | ||
| Type/Model | GCS | |
| Country of Origin | ||
| 1 | Description of Function | |
| 1.1 | It is group of low voltage switchgear withdrawable cabinet that can be operated easily and safely. | |
| 2 | Operational Requirements | |
| 2.1 | Electrical supply can be disconnected manually and automatically during overload and short-circuit. | |
| 3 | System configuration | |
| 3.1 | Low voltage switchgear withdrawable cabinet with all the essential components and copper busbar | |
| 4 | Technical Specifications | Ratings |
| 4.1 | Main circuit rated voltage | 400V |
| 4.2 | Rated frequency | 50Hz |
| 4.3 | Rated insultation voltage | 690V (1000V) |
| 4.4 | Maximum working current of main busbar (copper) | 1000A |
| 4.5 | Rated withstand current of main busbar | 100KA/1s |
| 4.6 | Protection Level | IP40 |
| 4.7 | Operating Mode | Manual and Automatic |
| 4.8 | Metal drawer type | 8E or 16E or Equivalent |
| 4.8.1 | 400A Drawer | 1 No. |
| 4.8.2 | 300A Drawer | 1 No. |
| 4.8.3 | 250A Drawer | 1 No. |
| 4.8.4 | 200A Drawer | 2 No. |
| 4.8.5 | 150A Drawer | 2 No. |
| 4.8.6 | 100A Drawer | 2 No. |
| 4.9 | Outer Dimension | Approx. (80cm X 105cm X 220cm) |
| 4.10 | Each drawer must have 3-digital or analog ammeter to measure 3-phase (R-Y-B) current individually | |
| 4.11 | Busbar must be of copper three phase four wire with protective Earthing (R,Y,B,N,PE). | |
| 4.12 | The MCCB should be of high quality & sensitive | |
| 4.13 | The operating mechanism of the drawers must be easy and smooth. | |
| 4.14 | Drawer Handle must be highly insulated and strong | |
| 4.15 | The outer dimension should approx match to (80cm X 105cm X 220cm) | |
| 4.16 | The outer design and color should match as per the design as shown in picture | |
| 5 | Busbar Tray | |
| 5.1 | The busbar tray must be installed at the top of the compartment of the functional unit, and the connection line and the common power lne can be put in the tray | |
| 5.2 | The required number of Busbar should be connected from existing system to installed cabinet by nut-bolt/ Busbar trunking system as per requirement | |
| 6 | Accessories, spares and consumables | |