Low Voltage Switchboard

Low Voltage Switchboard

The low-voltage draw out type switch cabinet is suitable for the power generation and supply system with three-phase AC frequency of 50Hz, rated working voltage of 380V and rated current of 4000A and below, which is used for power, distribution, motor centralized control and capacitance compensation. It is widely used in power plants, petroleum, chemical industry, metallurgy, textile, high-rise buildings and other places. The product conforms to iec60439, gb7251.1, JB / t9661 and other standards

Description

Low Voltage Switchboard


The low-voltage draw out type switch cabinet is suitable for the power generation and supply system with three-phase AC frequency of 50Hz, rated working voltage of 380V and rated current of 4000A and below, which is used for power, distribution, motor centralized control and capacitance compensation. It is widely used in power plants, petroleum, chemical industry, metallurgy, textile, high-rise buildings and other places. The product conforms to iec60439, gb7251.1, JB / t9661 and other standards


Operating environment:

1)Ambient temperature:-10°C-+40°C;

2)Altitude: high voltage ≤1000Meter, low voltage ≤2500Meter (technical department will design specially if exceeds);

3)Relative humidity:≤85%

4)Seismic intensity:≤ magnitude 8;

5Apply to the places have no fire,no explosion danger, no serious pollution,no chemical corrosion and no violent vibration.


Executive standard:

GB7251 Low voltage complete set switchgear and control device

GB3906-2006 3.6kV~40.5kV AC metal enclosed switchgear and control device


The main technical parameters:

Rated isolation voltage: 660V, 1000V

Rated working voltage: 380V, 660V

Rated voltage of auxiliary circuit: AC220V, 380V, DC110V, 220V

Rated frequency: 50Hz~(60)Hz

Rated current: horizontal bus ≤3150A; vertical bus 630A, 800A, 1200A

Rated short-time withstand current: t50KA

Rated peak current: 50KA / 0.1s

Short-circuit breaking capacity: 50kA (effective value)

IP rating: IP30, IP40

Bus configuration: three-phase four-wire, three-phase five-wire

Operation mode: manual, remote control, automatic



Parameter

Rated voltage

V

400

690

Rated insulation voltage

V

690

1140

Rated impact withstand voltage

V

6000

10000

Rated working short circuit breaking ability

kA

18~100

10~75

Rated utmost short circuit breaking ability

kA

25~120

20~85

Rated frequency

Hz

50/60

Rated current

A

400,500,630,800,1000,1250,1600,2000,2500,3150,4000,5000,6300

Rated control power

V

AC 110/220/380,DC 110/220

Dimension

(Unit:mm)

MNS/GCS/GGD

width

400,600,800,1000,1200

depth

600,800,1000

height

2200



Our low voltage switchboards(switchgears) have two models, GCK and GCD. GCK Low voltage withdrawable switchgears are specially engineered for power distribution and electric motor control operations. It is suitable for 380V alternating current three phase four line and three-phase five line systems.


Detailed explanation of common faults in low-voltage distribution cabinets:

1、 The circuit breaker cannot be closed.


1. The undervoltage coil is not working (the voltage is normal). Solution: Replace the undervoltage coil.

2. Press the closing button, and the closing coil will not work when powered on. Solution: Replace the undervoltage coil.

3. Poor contact of the close button. Solution: Replace the close button.

The fuse core of the control circuit is burnt out. Solution: Confirm that the control circuit is normal and there is no short circuit before replacing the fuse.

5. The circuit breaker does not store energy. Solution: Check that the motor control power supply voltage needs to be ≥ 85%.

6. The closed electromagnet controls the power supply voltage to be less than 85%. Solution: The power voltage of the closing electromagnet needs to be ≥ 85%.

7. The closing electromagnet is damaged. Solution: Replace the closing electromagnet.

8. Poor contact in the secondary circuit of the drawer type circuit breaker. Solution: Shake the drawer type circuit breaker out and then move it to the "open" position. Check if the secondary circuit connection is reliable.

9. The universal transfer switch is in the stop position. Solution: Turn the switch to the left or right power transmission.


2、 The main switch of the incoming cabinet cannot be turned on.


1. Poor contact of the start button. Solution: Replace the open button.

2. The open coil is burnt out. Solution: Replace the open coil.

3. The main reactive power meter is reversed or not rotating. The power factor of capacitor compensation is too high. Solution: Adjust the capacitance compensation to 0.92-0.97.

4. Transformer incoming line phase sequence error. Solution: Readjust the phase sequence.

3、 The voltage and current circuit is normal.

Solution: Replace the reactive power meter.


4、 The capacitor cabinet cannot be automatically switched.


1. The current sampling signal line is not connected. Solution: Connect the current sampling signal line.

2. Check if the controller fuse core is burnt out. Solution: Replace the fuse.

3. The voltage is too high, and the controller displays overvoltage. Solution: Adjust the overvoltage protection point.

4. The current is too low, and the controller displays it in advance. Solution: Automatically works normally when the current increases.

5. Capacitor cabinet (distribution cabinet related type: box type substation | distribution box) Compensator indicates overvoltage. Solution: Adjust the set voltage value to be higher than the actual voltage value.

6. The current sampling signal line is not connected. Solution: Connect the current sampling signal line.

7. The melting core of the compensation controller is burnt out. Solution: Replace the fuse.

8. The current is too low. Solution: Further debugging and processing after increasing the current.


5、 The electricity meter in the drawer doesn't turn.


1. Check if the secondary plug-in has poor contact. Solution: Adjust the secondary plug-in contact strip.

2. Both current and voltage are normal. Solution: Replace the electricity meter.


6、 Dual power switching cannot be automatically switched.


1. The universal transfer switch is not turned to the automatic position. Solution: Turn the switch to the automatic position.

2. The manual transfer switch did not switch to the automatic position. Solution: Turn the automatic transfer switch of the handle to the automatic position.

3. The undervoltage release device is not closed. Solution: Check if the voltage is consistent with the voltage level of the release, V ≥ 85%.

4. The time relay does not close. Solution: Check if the contact voltage of the time relay is normal.

5. The shunt mechanism of the circuit breaker does not reset. Solution: Check if the mechanical interlock is loose or stuck.


7、 The power factor of the capacitor cabinet cannot exceed 0.9.


1. The capacity of the capacitor decreases. Solution: Replace the capacitor.

2. Some circuits are not powered. Solution: Check and replace.

3. The original design load has increased. Solution: Increase the compensation capacity of the capacitor cabinet.


PRODUCT PHOTO

MNS (5)

MNS (6)

MNS()2

withdrawable (4)

FACTORY

CERTIFICATE


CQC

A

EXHIBITION


COMPANY OVERVIEW

Henan Fengyuan Power Technology Co., Ltd. was established in 2010 and is an industrial giant specializing in the production of power distribution equipment. After more than ten years of development, we have become an innovative enterprise engaged in the research and development, production and customization of electrical equipment.

PACKING&DELIVERY


baozhuang_

FAQ:

Q: Are you a factory or a trading company?

A: We have our own factory, and our trading team has rich experience in foreign sales.

Q: How about your company's quality control?

A: We pay attention to quality control from beginning to end to ensure that our products meet the quality CCC, ISO9001:2000 standards

Q: When is your delivery time?

A: Within 30 days after receiving the deposit.

Q: Is it possible to make a customer brand name?

A: Yes.

If the quantity exceeds the MOQ, OEM production is welcome.

MORE VIDEO


Facebook

https://www.facebook.com/bob.niu.35/


Youtube

www.youtube.com/channel/UC5IP4dL0UTQG4fgAOa3UhWA


Twitter

https://twitter.com/FengyuanE


This product is usually customized.

We are a manufacturer and have a professional technical department that can design and provide solutions according to customer needs.

Please contact our sales personnel to obtain design drawings

Here are our customer examples for your reference

Welcome to inquiry


Contact information:


Jiyuan Fengyuan Electrical Equipment Co., Ltd


Sales Department


Contact person:Mr Charles Du


E-mail:fengyuan800@outlook.com


Mobile:+8618639199897(Available for whatsapp,wechat,skype)


Add:Huling industrial zone,jiyuancity,henan province,China


TEL:+86-0391-2180800


FAX:+86-0391-2180818


Hot Tags: low voltage switchboard, China, manufacturers, suppliers, customized, low voltage electrical switchgears, Gck Low Voltage Draw out Switchgear, Power Distribution Panel, low voltage Withdrawable type switchgear, Complete Set Switch Cabinet, Vacuum Circuit Breaker For RMU