GCS
video
GCS

GCS Type Low Voltage Complete Set Switch Cabinet

The GCS type low voltage complete set switch cabinet device is developed by our company according to the development trend of China's low-voltage switchgear, after improving the selection of electrical components and cabinet structure. It is a series of modular and multifunctional...

Description

The GCS type low voltage complete set switch cabinet device is developed by our company according to the development trend of China's low-voltage switchgear, after improving the selection of electrical components and cabinet structure. It is a series of modular and multifunctional low-voltage power distribution cabinets that can meet various requirements of users.


This low-voltage switchgear complies with GB7251-1991 and JB/T9661.


Scope of application

GCS type low-voltage withdrawable switchgear (hereinafter referred to as the device) is suitable for power distribution systems in power plants, petroleum, chemical, metallurgy, building materials, textiles and other industries. Suitable for large-scale power plants, petrochemical and other places with high degree of automation and computer ports, as 50 (60) Hz, rated voltage 380V (400) (660), rated current three-phase AC low-voltage complete set of power distribution equipment for power distribution , The reactive power compensation current of the motor center control and power distribution system is less than 4000A.


Technical features:

■Increase the heat dissipation capacity of the connector, and greatly reduce the additional heat rise of the connector plug and socket, cable terminal, and partition caused by the heat of the connector.

■The separation between functional units and compartments is clear and reliable. The failure of one unit will not affect other units that can keep the failure to a minimum.

■The horizontal bus layout ensures that the equipment has good kinetic energy and thermal stability. It ensures that the device can withstand a short-circuit current of 80/176KA.

■The maximum number of circuits for a single MCC cabinet is 22. It can meet the requirements of large single motors in power plants and petrochemical industries.

■The connection between the equipment and external cables should be in the cable room. The cables can be input from the top and bottom. The zero sequence current transformer is placed in the cable room, which is easy to install and maintain.

■The power distribution system of the same power supply can limit the short-term current through the current-limiting reactor to stabilize the busbar at a certain value and reduce the requirements for the short-circuit strength of the components.

■The number of auxiliary connectors in the withdrawable unit (20 pairs in 1/2 unit, 32 pairs above 1 unit) can meet the requirements of computer ports and automatic control circuits.


Power switchgear service condition

■The highest ambient temperature is +40℃, the lowest is -5℃, and the 24-hour average temperature is the highest +35℃.

■The air is clean, the maximum relative humidity is 50% at a temperature of +40°C, and more relative humidity is allowed at a lower temperature, such as 90% at +20°C. Considering temperature changes, condensation may occasionally occur.

■The highest altitude is 2000m

■The pollution level is 3rd.

■Storage and transportation: -25℃~55℃. In a short time (not more than 24 hours) + 70°C.

■In this case, do not damage the equipment. Under normal circumstances, it should work normally.


■If the above service conditions cannot be met, the user should contact the manufacturer.


Main technical parameters:


Main circuit rated voltage (V)


AC380(400).(600)

Auxiliary circuit rated voltage (V)


AC220.380(400)

DC110.220

Rated frequency (HZ)


50(60)

Rated insulation voltage (V)


660(1000)

Rated current (A)

Horizontal bus bar

≤4000

Vertical bus bar (MCC)

1000


Bus bar rated short-time withstand current (KA/1s)

50.80


Bus bar rated peak withstand current (KA/0.1s)

105.176


Power frequency test voltage

(V/1min)

Main circuit

2500

Auxiliary circuit

1760


Bus bar

3 phase 4 line

A.B.C.PEN

3 phase 5 line

A.B.C.PE.N


Protection grade

IP30.IP40



Ordering instructions

Following contents should be included in purchase contract:

■All types of products (including main circuit plan number and auxiliary circuit plan number)

■Main circuit system combination timing diagram

■Auxiliary circuit schematic diagram

■Cabinet Components List

■The voltage, current, time and other setting parameters in the circuit

■Cabinet painting color

■Other special requirements

Hot Tags: GCS Type Low Voltage Complete Set Switch Cabinet, China, manufacturers, suppliers, customized, Power Switchgear, Power Distribution Cabinet, Metal Low Voltage Power Distribution Box, three phase switchgear, Low Voltage Switchgear Cabinet, Complete Set Switch Cabinet