Technical Requirements For Oil Immersed Transformers

Nov 14, 2023

Technical requirements for oil immersed transformers

1. Oil immersed transformer body: The high-voltage winding is wound with copper wire, and the low-voltage winding is wound with copper foil. The coil adopts glass fiber imported epoxy resin fully vacuum injection, with extremely strong stiffness and mechanical strength, good short-circuit resistance, and balanced ampere turns for high and low voltage coils. The epoxy resin glass fiber mixture has the same thermal expansion coefficient as the copper conductor, ensuring that the coil does not crack. Strong heat dissipation performance. Configure a temperature display and control system to automatically display the temperature of the three-phase winding of the transformer. When the limited temperature is reached, the temperature controller can automatically send a signal to control the start/stop, over temperature alarm, and protection of the fan. Two pairs of passive contacts are provided for automatically starting the exhaust fan of the substation. The iron core and all exposed metal components should undergo rust prevention treatment. The nameplate is made of stainless steel, and important data related to the transformer is marked on the nameplate according to the standard. The shell is assembled on site and made of stainless steel plate. It has a communication 485 interface and can transmit the operating status of the transformer.

2. The oil immersed transformer operates with load and does not exceed the temperature when the fan is not running; Under normal operation of the fan, it is allowed to operate with an overload of 50%, without overheating, alarming, or tripping.

3. Oil immersed transformer no-load loss: The no-load loss shall be manufactured according to the standard negative error, and shall not be a positive error. It shall comply with the new implementation standard of Shandong Electric Power Company.

4. Noise index: When the fan is not running normally, the 2000KVA transformer is below 52ab.

5. Creepage specific distance: Organic material not less than 20mmKV, ceramic not less than 18mm/KVo20, high-voltage side phase to ground and phase to phase clean air safety net distance (live part) 2125mo

6. The high-voltage incoming line is a cable that meets the needs of upper or lower incoming lines; The low-voltage outgoing line is a busbar duct, with upper outgoing line.

7. There should be access doors and windows in the front and back of the cabinet for easy inspection of various joints.

8. Equipped with a temperature measurement device and equipped with a temperature control box; The microswitches inside the control box should be accurately provided by the manufacturer. All components should use reinforced insulation products identified by "two parts".

9. The grounding wire terminal (10cm) should flow out at a suitable position, and the rest should be painted with corresponding phase color paint.

10. Under normal working and load conditions, the operating life of the transformer is 30 years

PRODUCT LINK

http://www.switchgear-china.com/power-distribution-transformer/oil-immersed-transformer/low-loss-power-transformer.html

PRODUCT PHOTO

20230320093321

20230320093328

20230320093334

20230512090945

20230512091119

20230512093151

H59

H61

This product is usually customized.
We are a manufacturer and have a professional technical department that can design and provide solutions according to customer needs.
Please click on the button below to send us the information, and our sales personnel will contact you to provide you with the design drawings

Here are our customer examples for your reference

Russian clients

Data Sheet N° 1-A: Transformer H61 20kV/400V of 160 kVA

DESIGNATIONS

UNITS

SPECIFIC DATA

CANDIDATE DATA

Maker

To be indicated

Reference standard

IEC 60076

Type

Phase

Vat

Hermetic

Execution

Tropicalized

Dielectric

PCB-free oil

Installation

On pole

Operating ambient temperature

°C

45

Rated frequency

Hz

50

Rated power

Kva

160

Rated primary voltage

Kv

20

Isolation level assigned to primary school

Kv

24

Number of phases in primary school

03

Secondary voltage

V

400/230

Voltage adjustment range on the M side when unladen

%

±2.5

Coupling

DYn11

Short circuit voltage

%

4 – 4.5

Neutral sized for one load

%

100

Maximum vacuum losses

W

230 - 460

Losses due to Maxi load

W

1450 - 2350

Maximum steady-state oil temperature

°C

55

Maximum temperature of the windings in steady state

°C

60

Winding material

Electrolytic copper

Maximum noise level

Db

52

50Hz industrial frequency hold, 1 min

Kv

50 – 70

Shock wave resistance (1.2/50 micros)

Kv

125 - 170

Cooling

ONAN

Nameplate

01

Grounding connection

01

Dimensions Height/width/depth

mm x mm x mm

1200 X 1270 X 820

Total mass of transformer including oil

Kg

700

Oil mass

Kg

160

PAINT

Tropicalized and anti-rust

Number

Layers

Binder

Colour

Plans and technical diagrams to be provided.

 