KYN28-12 Medium Voltage Metal Clad Power Switchgear

Aug 26, 2022

Main technical parameters

Rated voltage

.....................................

kV

3.6、7.2、12

Rated frequency

.....................................

Hz

50

Rated current of circuit breaker

.....................................

A

630/4000

Rated current of switchgear

.....................................

A

630/4000

Rated short-time withstand current (4S)

.....................................

kA

20、25、31.5、40

Rated peak withstand current (peak)

.....................................

kA

50、63、80、100

Rated short-circuit breaking current

.....................................

kA

20、25、31.5、40

Rated insulation level 1min power frequency withstand voltage

Pole-to-pole, pole-to- ground

kV

24、32、42

Between open contacts

kV

24、32、48

Lightning impulse withstand voltage (peak)

Pole-to-pole, pole-to- ground

kV

40、60、75

Between open contacts

kV

46、70、85

The shell is IP4X, and it is IP2X when the compartment door and circuit breaker chamber door are opened



Service Conditions

 

◎ Ambient airtemperature: -15°C~+40°C;

 

◎ Relative humidity: Daily average 95%,and daily average of water vapor pressure < 2.2kPa;

◎ Monthly average «90%, and monthly verage of water vapor pressure < 1.8kPa;

© Altitude: ^1000m;

◎ Seismic intensity: not beyond Ms8.

◎ Ambient air should be free of pollution of corrosive or flammable gas or vapor;

◎ No obvious vibration;