GCS Electrical Control Switchgear Panel

Sep 26, 2022

Installation environment


1.Ambient air temperature: -15℃ ~ +40℃;The daily average temperature shall not be higher than +35℃. If it exceeds, it will be designed separately according to the actual situation. 2.Altitude: 2000m and below. 3.Relative humidity: no more than 50% when the maximum temperature is +40℃, and larger relative humidity is allowed at lower tempertature; If it is 90% at +20℃, it shall be considered the influence of condensation may occur occasionally due to the change of temperature. 4.The installation inclination shall not exceed 5 degrees, and the whole cabinet column shall be relatively flat. 5.The switchgear shall be installed in a place without violent vibration and impact and make the electrical components subject to undue corrosion. Note: when user have special requirements, the comany will coordinate and solve them.



Main technical parameter



Rated voltage of main circuit(V)
AC 380(400)、(660)
Rated voltage of auxiliary circuit(V)
AC 220/380(400) DC110、220
Rated frequency(Hz)
50(60)
Rated insulation voltage(V)
660(1000)
Rated current(A)
Horizontal Bus-bars
≤6300
Vertical Bus-bars(MCC)
1000
Rated short-time withstand current of bus(kA/1s)
50,80
Rated peak withstand current of bus(kA/1s)
105,176
Power frequency test voltage(V/1min)
Main circuit
2500
Auxiliary circuit
17600
Generatrix
TN-C
A、B、C、PEN
TN-S
A、B、C、PEN、N
IP code
IP30、IP40






Welcome to inquiry


Contact information:


Jiyuan Fengyuan Electrical Equipment Co., Ltd


Sales Department


Contact person:Mr Charles Du 


E-mail:fengyuan800@outlook.com


Mobile:+8618639199897(Available for whatsapp,wechat,skype)


Add:Huling industrial zone,jiyuancity,henan province,China


TEL:+86-0391-2180800


FAX:+86-0391-2180818