Use conditions of GCS low voltage switchgear
Jul 20, 2021
1. The ambient air temperature is not higher than +40°C and not lower than -5°C. The average temperature within 24 hours must not be higher than +35°C. When it exceeds, the capacity should be reduced and run according to the actual situation.
2. For indoor use, the altitude of the place of use shall not exceed 2000m.
3. The relative humidity of the surrounding air does not exceed 50% when the temperature is +40°C, and a larger relative humidity is allowed at a lower temperature. If +20°C is 90%, it should be considered that the influence of condensation may occur occasionally due to temperature changes.
4. When the device is installed, the inclination to the vertical surface is not more than 5°, and the whole group of cabinets is relatively flat (in accordance with the GBJ232-82 standard).
5. The device should be installed in a place where there is no violent vibration and impact and not enough to cause undue corrosion on electrical components.
6. When users have special requirements, they can negotiate with our company to solve them.