Introduction to Common High Voltage Switch Cabinet Products KYN28 High Voltage Cabinet

Jul 25, 2023

Introduction to Common High Voltage Switch Cabinet Products KYN28 High Voltage Cabinet

KYN28A-12 indoor metal armored withdrawable switchgear is mainly used for power plants, industrial and mining enterprises, as well as secondary substations in the power system for power collection, transmission, and starting of large motors. Implement control, protection, real-time monitoring, and measurement. It has perfect five prevention functions. It can be equipped with Zhekai VS1 (ZN63A-12) vacuum circuit breaker, VD4 vacuum circuit breaker produced by ABB, HS type (ZN82-12) vacuum circuit breaker produced by Fuji Electric Switchgear Co., Ltd., and VEP type (ZN96-12) vacuum circuit breaker produced by Xiamen Huadian Switchgear Co., Ltd., a Sino foreign joint venture. At present, it is widely used in the 12KV market.

1. Model Meaning

KYN28A-12- □ --- □

Environmental characteristics of armored cabinets: removable primary solution number: design number: indoor

2. Overall dimensions of the cabinet: (standard overhead incoming and outgoing line scheme; cable incoming and outgoing line scheme)

*Standard scheme for cable inlet and outlet lines and contact cabinets: width 800 (1000) × 1500 deep × 2300 high

*Standard scheme for overhead incoming and outgoing lines: width 800 (1000) × Deep 1660 × 2300 high

Note: 1. GZS1+cable inlet and outlet line and contact cabinet standard scheme: width 650 × 1500 deep × 2300 high; The spacing between phases is 150mm; The phase spacing of the GZS1 cabinet with a width of 800 is 210mm; The spacing between cabinets with a width of 1000 is 275mm;

3. Product structure and appearance:

KYN28A-12

5. Introduction to Five Prevention Interlocking:

(1) When the handcart is closed in the working position of the cabinet, the locking electromagnet inside the chassis of the handcart is locked on the screw and will not be pulled to prevent the handcart from accidentally pulling the circuit breaker with load.

(2) When the grounding switch is in the closed position, the push rod in the interlocking mechanism of the grounding switch spindle is pushed into the handcart guide rail in the cabinet, so the equipped circuit breaker handcart cannot be pushed into the cabinet.

(3) After the circuit breaker handcart is closed in the working position, the outgoing side is electrified, and the grounding switch cannot be closed at this time The push rod in the interlocking mechanism of the grounding switch spindle is blocked, and its operating handle cannot operate the grounding switch spindle

(4) For cable entry cabinets; For bus section cabinet and transformer scheme, since the incoming cable side is electrified, Electromagnetic lock is installed on the lower door to ensure that the cable chamber cannot be entered when the cable side is electrified;

(5) By installing an error proof transfer switch (with red and green signs) on the panel, it is possible to prevent accidental opening and closing of the circuit breaker

6. Operating procedures

Power transmission operation:

First install and then seal the board, Close the front and lower doors again - - - Operate the grounding switch spindle and open it - - - Use a transfer vehicle (platform vehicle) to push the handcart (in the open state) into the cabinet (test position) - - - - Insert the secondary plug into the static socket - - - (test position indicator on) - - - - - (close the front and middle doors) - - - - - Use the handle to push the handcart from the test position (open state) to the working position - - - - (work position indicator on, test position indicator off) ---------Closing circuit breaker handcart

Power outage (maintenance) operation:

Opening the circuit breaker handcart - - - - Use the handle to exit the handcart from the working position (opening state) to the test position - - - - (The working position indicator is off, and the test position indicator is on) - - - - Open the front middle door - - - Pull out the secondary plug from the static socket - - - (The test position indicator is off) - - - - - Use the transfer vehicle to open the handcart (in the opening state) Exit the cabinet ------- Operate the grounding switch spindle and close it ------- Open the rear sealing plate and front lower door

★. Attention: The lower lightning arrester handcart and the middle (lower) PT handcart can be directly pulled out of the cabinet during busbar operation

PRODUCT LINK

http://www.switchgear-china.com/switchgear/high-voltage-switchgear/33-kv-40-5-kv-high-voltage-switchgear.html

PRODUCT PHOTO

inside

KYN28A

KYN28A-12 1

KYN28A-12 2

KYN28A-12 123

KYN28A-12

KYN28A-12 5

This product is usually customized.