40.5kv Power Switchgear
KYN61-40.5kv power switchgear has the function of "five preventions": prevent misoperation of the circuit breaker, prevent pushing and pulling the handcart with load, prevent the ground wire from being connected to the ground, prevent power transmission with the ground wire, and...
Description
KYN61-40.5kv power switchgear has the function of "five preventions": prevent misoperation of the circuit breaker, prevent pushing and pulling the handcart with load, prevent the ground wire from being connected to the ground, prevent power transmission with the ground wire, and prevent inadvertently entering the charged interval function.
It is suitable for three-phase AC 50Hz, rated voltage 35kV power distribution system for receiving and distributing electric energy. This type of switchgear is a complete set of indoor protection devices and is not installed against the wall.
Normal environmental conditions
1. The upper limit of ambient air temperature: +40℃, the lower limit: -10℃, and the daily average temperature does not exceed 35℃;
2. The altitude does not exceed 1000m;
3. The relative ambient temperature is not more than 95% daily, and the monthly average is not more than 90%;
4. The earthquake intensity does not exceed 8;
5. The daily average value of water vapor pressure does not exceed 2.2Kpa, and the monthly average value does not exceed 1.8kpa;
6. There is no fire, explosion hazard, serious pollution, chemical corrosion and severe place in this building.

No. | Items | Unit | Parameters | ||
1 | Rated voltage | KV | 40.5 | ||
2 | Rated frequency | Hz | 50 | ||
3 | The main busbar rated current | A | 1250,1600,1200 | ||
4 | Branch busbar rated current | A | 630/1250/ 1600 | ||
5 | Rated insulation level | Power frequency withstand voltage in 1min (Effective value) | Phase-phase, Phase-ground | KV | 95 |
Primary isolation fracture | KV | 115 | |||
Lightning Impulse Withstand Voltage (peak value) | Phase-phase, Phase-ground | KV | 185 | ||
Primary isolation fracture | KV | 215 | |||
Power frequency withstand voltage of auxiliary control circuit | V | 2000 | |||
6 | Rated short circuit breaking current | KA | 25/31.5 | ||
7 | Rated short circuit closing current (peak value) | KA | 63/80 | ||
8 | Rated short-time withstand current (4S) | KA | 25/31.5 | ||
9 | Rated peak withstand current | KA | 63/80 | ||
10 | Rated voltage of auxiliary control circuit | V | -110,-220,~220 | ||
11 | Protection grade | Enclosure IP4X, IP2X When the door of the circuit breaker opens | |||
12 | Outline size (width * depth * height) | mm | 1400(1200)*2800(2600)*2600(*includes an internal digital SF6 handcart scheme) | ||