How To Shield The Electromagnetic Leakage Points in Various Modules in The Prefabricated Substation

Aug 07, 2023

How to shield the electromagnetic leakage points in various modules in the prefabricated substation

 

 

For electromagnetic leakage protection of prefabricated cabin ventilation holes, metal shielding covers can be installed to deal with it. The structure of the metal shielding cover should be designed specifically based on the factors that affect the shielding performance of the holes. The factors that affect the shielding performance of the holes mainly include the maximum size, depth, spacing, and number of holes. Due to the intelligence of shielding effectiveness being related to the maximum size of the hole, and not directly related to the area of the hole, circular holes should be opened on the metal shielding cover of the cabin vent as much as possible to minimize the maximum size of the hole while maximizing the ventilation area.

 

For the electromagnetic leakage protection of prefabricated cabin door gaps, a metal conductive spring can be installed at the contact position between the door and the door frame to directly form electrical continuity between the door and the door frame, thereby avoiding electromagnetic leakage at the door gap. In order to save costs, when pasting metal conductive springs, a certain distance interval and intermittent pasting can be used. The minimum distance between metal springs should be less than one fourth of the electromagnetic radiation wavelength.

For electromagnetic leakage in the gaps of prefabricated cabin air conditioners, conductive sealant can be used to create electrical continuity between the air conditioning shell and the metal sealing plate of the cabin.

 

In addition, external cables enter the cabin through the inlet and outlet holes, which is also an important channel for electromagnetic leakage. Therefore, all cables entering and exiting the cabin use shielded cables, and the shielding layer of the cables should be grounded at both ends. The use of spare cores inside the cables to replace the shielding layer grounding should be strictly avoided.

The protection of internal electrical components in prefabricated cabins is not limited to shielding against wind, sand, rain, and dust, but electromagnetic shielding is also an important role of prefabricated cabins. The shielding method of electromagnetic leakage points in the prefabricated cabin realizes the electrical continuity of parts, improves the shielding performance of the prefabricated cabin, optimizes the internal Earthing system, and effectively improves the stability of the operating state of electrical equipment.

 

PRODUCT LINK

http://www.switchgear-china.com/box-type-compact-substation/prefabricated-substation/prefabricated-box-type-substation.html

 

PRODUCT PHOTO

20230602101502

20230602101509

20230602101515

20230602101533

20230602101552

20230427155118

20230427155230

20230427155239

 

 

This product is usually customized.
We are a manufacturer and have a professional technical department that can design and provide solutions according to customer needs.
Please click on the button below to send us the information, and our sales personnel will contact you to provide you with the design drawings

 

Here are our customer examples for your reference

Afghan clients

TECHNICAL REQUIREMENTS AND CHARACTERISTICS OF EQUIPMENT
Re:82 sets compact substation
Item-
No.
Schedule of Technical Data Unit Required (at
3000 m
Offered Data
System Data Requirements
1.05.10 Stranded copper conductor for earthing
Manufacturer -
Material - copper
Cross-section mm2 >50
Length m >40
1.05.11 Earthing rods
Manufacturer -
Type -
Materia! -
Length m
Sections per rod pcs
1.6 Compact Substations (Option 1)
Manufacturer - fengyuan
Type - OutDoor
Overall protection class for complete substation - IP 44 IP 44
Material of enclosure - GI
Overall dimensions (W x L x H)
for S/S with 1x50 kVA transformer mm/mm/mm 3000x1850x2150
■ for S/S with 1x100 kVA transformer mm/mm/mm 3000x1850x2150
for S/S with 1x160 kVA transformer mm/mm/mm 3000x1850x2150
• for S/S with 1x250 kVA transformer mm/mm/mm 3000x1850x2150
Overall weight
■ for S/S with 1x50 kVA transformer kg 1000kg.
■ for S/S with 1x100 kVA transformer kg 1000kg.
■ for S/S with 1x160 kVA transformer kg 1000kg.
■ for S/S with 1x250 kVA transformer kg 1000kg.
1.6.1 20 kV Switchgear equipment
Manufacturer - Chnt / Equivalent
Type - Indoor RMU

 

IF NEED MORE DETAILES,PLEASE FEEL FREE YO CONTACT US