KYN61-40.5 Metal-clad Enclosed 300A Power Cabinet

KYN61-40.5 removable AC metal-clad switchgear applies to 40.5kV, 3 phase, AC and 50/60Hz electrical power network for receiving and distributing power energy and also for control, monitor and protect ion. It is applicable in general power system and occasions with frequent operation. The product conforms to GB3906: 3~35kV AC Metal Enclosed Switchgear, IEC60694 & GB/T11022: The common technical clauses of HV Switchgear and controlgear Standard, DL/T404-1997: Order Technical term of Indoor AC HV Switchgear and IEC62271-200 1~52kV AC Metal Enclosed Switchgear and controlgear standard.

Description

KYN61-40.5 metal-clad enclosed 300A power cabinet

Model

KYN61-40.5

Rated voltage

40.5

Frequency

50HZ

Rated Current

1250A/1600A/2000A

IP Grade

IP3X

Environment Temperature

-10 C~+40 C

Accessories

specification

Maintenance Instruction

Must be cleaned and put in a dry place

KYN61-40.5 switchgear is three phase AC 50 Hz,rated voltage of 40.5 KV indoor power distribution equipment.As power plants ,substations and industrial distruction of electric energy only ,and has a circuit implementation of control,protection and monitoring function .

Structure Description:

Switchgear according G83906 and IEC298 standards and design,And can be removed from the cabinet as a whole unit (trolley )components .
Cabinet structure are made of aluminum deposited zine plate or galvanized sheet assembled with both connection ,separate circuit breaker switchgear roon ,bus room ,cable room and instrument room,All metal components are grounded ,each compartment of the main circuit .system have separate pressure release channel in the cable compartment can be set 10*60mm ground bus .

Main characteristics:


1.The use of assembled cabinet structure ,circuit breaker handcart floorstanding structure ,
Samall size:
2.Optional: The company vacuum breaker VW1-40.5,xiamen huadian vacumm breaker VEP-40.5 ,similar circuit breaker are interchangeable .
3.Equipped with special transport vehicles can lift ,transport vehicles amd cabinet accurate positioning ,locking and reliable
4.The main switch ,handcart ,door interlock switch between mandatory mechanical locking methods are used to meet the ‘Five Anti’ interlock function .
5.all operation can be carried out at the door closed state ,to protect the safety of the operator .
6.Cable ample room space ,can be connected to multiple cables ,and overhead outlet .
7.Shell protection grade IP3X,handcart room door open between the various compartments protection class IP2X.
8.The material can be galvanized sheet can be deposited alumimum zinc plate production .

Environmental Conditions

1) Suitable Temperature: -10℃ ~ +40℃, Daily average temperature:≤35℃.

2) Suitable Altitude: ≤1000m

3) Relative Humidity: Daily mean ≤95%, monthly mean ≤90%

4) Gradation of Earthquake Damage: ≤ Level 8

Applicable occasions should be free from corrosives, inflammables and vapor.

Main Electric Parameters

No.

Items

Unit

Parameters

1

Rated voltage

KV

40.5

2

Rated frequency

Hz

50

3

The main busbar rated current

A

1250,1600,1200

4

Branch busbar rated current

A

630/1250/ 1600

5

Rated insulation level

Power frequency withstand voltage in 1min (Effective value)

Phase-phase,

Phase-ground

KV

95


Primary isolation fracture

KV

115

Lightning Impulse Withstand Voltage

(peak value)

Phase-phase,

Phase-ground

KV

185


Primary isolation fracture

KV

215

Power frequency withstand voltage of auxiliary control circuit

V

2000

6

Rated short circuit breaking current

KA

25/31.5

7

Rated short circuit closing current (peak value)

KA

63/80

8

Rated short-time withstand current (4S)

KA

25/31.5

9

Rated peak withstand current

KA

63/80

10

Rated voltage of auxiliary control circuit

V

-110,-220,~220

11

Protection grade

Enclosure IP4X, IP2X When the door of the circuit breaker opens

12

Outline size (width * depth * height)

mm

1400(1200)*2800(2600)*2600(*includes an internal digital SF6 handcart scheme)

13

weight

kg

~2300

 

What is a high-voltage switchgear

 

1、 Material of high-voltage switchgear cabinet body

1. Cold rolled steel plate or angle steel (used for welding cabinets);

2. Aluminum zinc coated steel plate or galvanized steel plate (used for assembling cabinets)

3. Stainless steel plate (non magnetic)

4. Aluminum plate (non magnetic)

2、 Functional units of high-voltage switchgear:

1. Main busbar room (generally arranged in two structures: "pin" or "1")

2. Circuit breaker room

3. Cable room

4. Relay and instrument room

5. Cabinet top small busbar room

6. Secondary terminal compartment

3、 Functions of the switchgear

The switchgear has functions such as overhead incoming and outgoing lines, cable incoming and outgoing lines, and busbar connection.

4、 Composition of switchgear

The switchgear should meet the relevant requirements of GB3906-1991 "3-35 kV AC Metal Enclosed Switchgear" standard, consisting of two parts: the cabinet body and circuit breaker. The cabinet body is composed of a shell, electrical components (including insulation parts), various mechanisms, secondary terminals, and wiring.

5、 Classification

According to the installation method of circuit breakers

According to the installation method of circuit breakers, they are divided into movable (handcart) and fixed types

1. Mobile or handcart (represented by Y): indicates that the main electrical components inside the cabinet (such as circuit breakers) are installed on withdrawable handcart. Due to the good interchangeability of handcart cabinets, it can greatly improve the reliability of power supply. Commonly used handcart types include isolation handcart, metering handcart, circuit breaker handcart, PT handcart, capacitor handcart, and used variable handcart.

2. Fixed type (represented by G): indicates that all electrical components inside the cabinet (such as circuit breakers or load switches) are installed in a fixed type, and fixed switch cabinets are relatively simple and economical.

By installation location

Divided into indoor and outdoor according to installation location

(1) For indoor use (represented by N): indicates that it can only be installed and used indoors;

(2) For outdoor use (indicated by W): indicates that it can be installed and used outdoors.

6、 According to the cabinet structure

According to the cabinet structure, it can be divided into four categories: metal enclosed armored switchgear, metal enclosed interval switchgear, metal enclosed box switchgear, and open switchgear

(1) The main components of metal enclosed armored switchgear (represented by the letter K), such as circuit breakers, transformers, busbars, etc., are respectively installed in grounded metal partitions separated by metal enclosed switchgear.

(2) Metal enclosed bay switchgear (represented by the letter J) is similar to armored metal enclosed switchgear in that its main electrical components are also installed in separate compartments, but have one or more non-metallic partitions that meet a certain level of protection.

(3) Metal enclosed box type switchgear (represented by the letter X) The switchgear enclosure is a metal enclosed switchgear.

(4) Open type switchgear, without protection level requirements, with some parts of the casing being open switchgear.

7、 Five prevention measures for high-voltage switchgear

1. After the vacuum circuit breaker car inside the high-voltage switchgear is closed in the test position, the car circuit breaker cannot enter the working position. (Prevent load closing)

2. When the grounding switch inside the high-voltage switchgear is in the closed position, the car circuit breaker cannot be closed. (Prevent closing with grounding wire)

3. When the vacuum circuit breaker inside the high-voltage switchgear is closed, the back door of the panel and cabinet is locked with a mechanical device on the grounding knife. (To prevent accidental entry into live compartments)

4. The vacuum circuit breaker inside the high-voltage switchgear is closed during operation, and the grounding switch cannot be put into operation. (Prevent live hanging of grounding wires)

5. The vacuum circuit breaker inside the high-voltage switchgear cannot exit the working position of the trolley circuit breaker when it is working and closing. (To prevent loaded knife brakes)

 

Products photo

kyn61-405 2

KYN61-405 3

kyn61-405 5

KYN61-405 6

KYN61-405 12

KYN61-405 13

Factory workshop

 

product-960-1274

Certificate

CQC

product-800-600

A

2

Packing&Delivery

baozhuang

product-752-497

Company overview

product-898-920

Exhibition

product-808-808

 

FAQ

 

Q5 : Is OEM/ODM available?

A: Yes, it is! Our products can be Customized. We have design and engineer teams,we can customize products according to customers' drawing or requirements.

Q6 : You are manufacturer or trading company?
A: We are factory, As a 100% professional manufacturer with 20 year's manufacturer experience, we could produce products according to customers' requirements and we could also control the quality of products 100%.

Q7 : Can the price be negotiated?

A: Yes, the price is negotiable. It can be changed according to your quantity or package

Q8 : How about inspection?

A: We have the whole inspection system from raw material to end products include temperature rise test,salt spraying test conductor type test,mechanical life test.

Q9 : What is payment terms?

A: T.T, Paypal,Western Union,Alibaba trade assurance and L/C is acceptable. 30% T/T in advance ,70% balance before shipment.

Q10 : What is the service offered by company?

A: We have the professional engineer team which can design and develop the mold to arrive different customer requirement.

We also have the sales team to offer good service from pre-sale to after-sale.

 

Customer Example

 

This product is usually customized.
We are a manufacturer and have a professional technical department that can design and provide solutions according to customer needs.
Please contact our sales personnel to obtain design drawings

Here are our customer examples for your reference

Ethiopian customers

Datasheet
1.1 710-512-01-MVS1 Main Substation
Incoming Switchgear A01 B01 2
No Components Specification Unit Qty Maker
1 VCB
HVX12-50-31-F 275mm
Altitude ≤2000m
Opening voltage DC220V
Closing voltage DC220V
Energy storage voltage DC220V
Set 1 China
2 VT JDZ-10 10KV/√3/0.1KV/√3 Set 3 China
3 CT
LZZBJ9-12 3000/1A 5P20 10VA
5P20 5VA 5Fs5 5VA
Set 3 China
4 High voltage fuse XRNP1-12 0.5A Pc 3 China
5 Lightning arrester HY5WZ-17/50 Set 3 China
6 Intelligent control panel WY-9008A Pc 1 China
7 Short circuit and ground fault indicator EKL-4-1 Pc 1 China
8 Multifunctional electric instrument PD666-3S3 380V 5A Pc 1 China
9 Primary harmonic eliminator LXQ-12KV Pc 1 Fengyuan
10 Charged display DXN-12Q Pc 1 China
11 Temperature and humidity controller WY-CS-III Pc 1 China
12 Connecting piece JY-2 Pc 3 China
13 Junction box PJ1 Pc 1 China
14 Metering bracket Universal type Pc 1 China
15 Signal lamp ND16-22D/4 AC380V red Pc 1 CHNT
16 Signal lamp ND16-22D/4 AC380V green Pc 1 CHNT
17 Signal lamp ND16-

 

IF NEED MORE DETAILES,PLEASE FEEL FREE YO CONTACT US

 

Hot Tags: kyn61-40.5 metal-clad enclosed 300a power cabinet, China, manufacturers, suppliers, customized, Armored removable switchgear, AC Metal enclosed Switchgears, hv switchgear Switchgear Cabinet, medium and high voltage switchgear, Switchgear Cubicle, AC switchgear

(0/10)

clearall