Indoor Vs1 12kv 2500A Side Mounted High Medium Voltage Vacuum Circuit Breaker
Widely used in power plants, substations, and other electrical equipment,as the protection and control of electrical facilities,especially for the place where the goods are frequently operated under rated current and the multiple breaking current.
Description
We make continuous efforts to really improve the quality of Metal Armored Removable Switchgear, Cast Resin Dry Type Transformer, compact switchgear and effectively drive the improvement of the quality of domestic related products. With the development and enlargement of mass clients abroad, now we have set up cooperative relationships with many major brands. We know that if we want to achieve rapid development, we must actively implement the strategy of quality, brand and standardization, we rely on independent research and development and innovation, so as to achieve product diversification, superior quality, comprehensive customers and service integration. Our company has its own spot warehouse and has a large number of inventory all year round in order to meet the needs of customers. With the integration of the global economy and the rapid development of industry, competition between companies has increased.
The side mounted indoor vacuum circuit breaker is suitable for 12kV voltage, as a protection and control unit of power equipment, industrial and mining enterprises, it can be used for switching loads of various kinds and frequent operation, repeatedly breaking short-circuit current situation. The product adopts new type of circuit breaker, a VSG part can adopt the international brand of embedded pole, the vacuum interrupter and the main circuit part is fixedly sealed into a whole, protect the interrupter from collision, dust and gel image, strong ability to adapt to the environment, greatly reduces the cost of operation and maintenance. The real implementation of the product part of a maintenance free, low maintenance operation mechanism;
Widely used in power plants, substations, and other electrical equipment,as the protection and control of electrical facilities,especially for the place where the goods are frequently operated under rated current and the multiple breaking current.
NO | Item | Units | Technical parameters | ||
1 | Rated voltage | KV | 12 | ||
2 | Rated short-duration power frequency withstand voltage | 42/48(Interphase, ground/fracture) | |||
3 | Rated lightning impulse withstand voltage | 42/48(Interphase, ground/fracture) | |||
4 | Rated frequency | Hz | 50 | ||
5 | Rated current | A | 630 1250 | 630 1250 1600 | 630 1250 1600 |
6 | Rated short-circuit breaking current | KA | 20/25 | 31.5 | 40 |
7 | Rated short-time withstand voltage | 20/25 | 31.5 | 40 | |
8 | Rated short circuit duration | S | 4 | ||
9 | Rated peak withstand current | KA | 50/63 | 80 | 100 |
10 | Rated short circuit closing current | 50/63 | 80 | 100 | |
11 | Secondary circuit power frequency withstand voltage (1min) |
| |||
12 | Rated single / back to back capacitor group breaking current | A | 630/400(40kA:800/400) | ||
13 | Rated capacitor bank closing current | 12.5 (frequency is not greater than) | |||
14 | Mechanical life | KA | 20000 | ||
15 | Rated current breaking times (electrical life) | 20000 | |||
16 | Rated short circuit current breaking times | times | 50(40KA≤30) | ||
17 | Dynamic and static contacts allow wear cumulative thickness | mm | 3 | ||
18 | Energy storage time | s | ≤10 | ||
19 | Contact opening distance | mm | 11±1 | ||
20 | Overtravel | 3.5±0.5 | |||
21 | Contact closing bounce time | ms | ≤2(40KA≤3) | ||
22 | Three-phase split/closed period | ≤2 | |||
23 | Average opening speed (contacts are separated by -8mm) | m/s | 1.2±0.2 | ||
24 | Main conductive loop resistance | 0.6±0.2 | |||
25 | Main conductive loop resistance | μΩ | ≤50(630A)≤45(1250A) | ||
26 | Rated operation sequence | 0-0.3s-Co-180s-Co | |||
Order instruction:
Complete model and order quantity of the product
Rated current, rated voltage, distance of each poles
Rated short circuit breaking current
Rated voltage of operation mechanism open and close release, rated voltage of energy saving motor
Required accessory and quantity
Other requirement please contact with us directly



We believe in integrity and innovation, and take customer demand as the guidance to provide customers with high-quality Indoor Vs1 12kv 2500A Side Mounted High Medium Voltage Vacuum Circuit Breaker solutions. We have introduced and trained a professional, qualified and innovative team of marketing management and technical elites. We give competitive price for quality solutions and we are going to make certain your shipment is handled quickly by our logistics department.
Hot Tags: side mounted indoor vacuum circuit breaker, China, manufacturers, suppliers, customized, Overhead Distribution Transformer, high voltage GIS switchgear, prefabricated substation 20 kv, low voltage switchgear and controlgear assemblies, Metal enclosed Switchgear Cabinet, Oil Power Transformer
[[ProKeywords]]Send Inquiry
You Might Also Like
-

11kv 500kVA Electric Voltage Power Oil-Immersed Tran...
-

Indoor Switchgear Ring Main Unit 36kv Gas Insulated
-

High-Tech Enterprise Electrical Automatic Wires and ...
-

Box-Type Substation Stainless Steel Enclosure
-

OEM Sheet Metal Fabrication Outdoor Cabinet Industri...
-

Fixed Electronic Transformer Ei-28 Low Frequency Low...